Cathodic Protection Products - Off-Shore

ICCP Amstel 1 N (replaced by a new type)

Range 6 to 50V  1 to 10A <200W

 

The Amstel 1 Type C is a compact and robust switch mode power supply, forced cooled, specifically designed for cathodic protection. Standard SCADA RS485 MODBUS fieldbus.

 

The Amstel Rectifier is Voltage and Current constant. The rectifier can be parameterized by the AM software RS485 or USB-B, and optionally parameterized using three push buttons by menu structure. The parameters can be protected by a PIN code to prevent unauthorized personnel to change settings.

Types 

Voltage

6V

8V

12V

16V

20V 

24V

30V

40V

50V

1A
2A
5A  
10A        
current                  

 

Features

  • Supply: 190V...230V.
  • Modbus over RS485.
  • RTU and ASCII protocol.  1200...115.200 baud (19.200 baud default).
  • Auto low voltage at no load.
  • Alarms on over-current, over-voltage.

Control and Display Panel 

  • Display actual Current & Voltage display
  • Optional Menu
  • Status Leds

- Power LED 

- Communication LED

- Output active LED

- Error LED

  • USB-B 

Connection panel

Power connector

  • Power 190Vac..240Vac 1ph

Fieldbus

  • RS485 half duplex MODBUS

Input/Output

  • 1x Digital inputs

DC output

  • Plus terminal
  • Min terminal

Fuse for the power supply

Standard air in.

Specifications

 Item Minimal Nominal Maximal Unit
 Environment temperature -20 +20 +35 oC
 Relative humidity 10 60 90 %
 Height     175 mm
 Width Horizonal version     110 mm
 Width Vertical version     75 mm
 Length Horizontal version     220 mm
 Length Vertical version     244 mm
 Weight  2,5   3 kg
 Electrical        
 Line voltage [AC] depending on type -5% 220 +5% V
 Max output power (depending on type)     200 W
 Standby power incl.   2   W
 Input fuse 5x20mm Slow   1.6   A
 Accuracy    <0.2   

PDN

PDN = AM1N-(DC Voltage)V-(DC Current)A-1-230V-CM1RF3RS1(Options)

Example

Amstel 1 16V 10A natural cooled 1ph 230Vac with modbus and Menu and ON/OFF potential control

AM1N-16V-10A-1-230V-CM1RF3RS1

Options

  • AF1

    Reverse air flow, bottom to top direction. 

  • M1

    Menu controlled with push buttons on top.  

  • PU1

    Cathodic protection Timer option.

  • RF1

    Cathodic protection potential controlled on ON value reference cell can be any type as long the...

  • RF2

    Cathodic protection potential controlled on OFF value reference cell can be any type as long the...

  • RF3

    Cathodic protection potential controlled on ON and OFF value reference cell can be any type as...

  • RS1

    RS485 Modbus RTU/ASCII open protocol easy to integrate with SCADA or other controls PLC etc.

  • TB1

    Vertical mounting holes Top and Bottom

  • US1

    USB parameterization option.